CZ05D

Air-cooled chiller with 50 kW cooling capacity. This low-energy low-noise machine is ready for use. The machine is mounted in a robust frame with a shock-resistant grid for condenser protection and can be moved easily with a forklift or crane.
CZ05D

Technical specifications

Cooling capacity 55.3 kW
Power consumption 24 kW
Current (nominal) 43 A
Current (start) 139 A
Frequency 50 Hz
Power connection 63 A CEE
Voltage 400 V
Recommended fuses 63 A
Phases 3 + N + A
Internal pump Nee
Water connection 2″ Bauer
Flow minimum (m³/h) 5 m³/h
Flow minimum (L/min) 83 L/min
Flow minimum (L/sec) 1.4 L/sec
Flow nominal (m³/h) 9.7 m³/h
Flow nominal (L/min) 160 L/min
Flow nominal (L/sec) 2.7 L/sec
Flow Maximum (m3/h) 19 m³/h
Flow maximum (L/min) 317 L/min
Flow (max.) 5.3 L/sec
Recommended volume 132 L
Maximum working pressure 10 bar
Nominal pressure drop 30 kPa
Sound level (at 5 m) 51 dB(A)
Sound level (at 1 m) 65 dB(A)
Length 2800 mm
Width 1200 mm
Height 1900 mm
Weight 916 kg
Sound level (at 10 m) 45 dB(A)