Low Temp chiller

Low temperature chiller with a cooling capacity of 200 kW. This low-temperature chiller uses the natural refrigerant CO2 with a GWP value of 1. This low-temperature chiller is suitable for output temperatures as low as -35 ˚C. Smart design eliminates any need for emergency cooling. The chiller is energy efficient, low-noise and plug and play. The chiller is housed in a robust frame and can easily be moved using a forklift or crane.
Low Temp chiller

Technical specifications

Cooling capacity 200 kW
Cooling capacity 200 kW
Power consumption 195 kW
Current (max) 372 A
Current (nominal) 355 A
Current (start) 276 A
Frequency 50 Hz
Power connection M12 boutverbinding
Voltage 400 V
Recommended Fuses 400 A
Phases 3 + A
Internal pump Ja
Water connection 4″ Bauer
Flow minimum (m³/h) m³/h
Flow minimum (L/min) L/min
Flow minimum (L/sec) L/sec
Flow nominal (m³/h) 44 m³/h
Flow nominal (L/min) 733 L/min
Flow nominal (L/sec) 12 L/sec
Flow Maximum (m3/h) m³/h
Flow maximum (L/min) L/min
Flow (max.) L/sec
Recommended volume 1500 L
Maximum working pressure 16 bar
Nominal pressure drop 56 kPa
Sound level (at 5 m) 60 dB(A)
Sound level (at 1 m) 67 dB(A)
Length 6100 mm
Width 2500 mm
Height 2600 mm
Weight 8180 kg
Sound level (at 10 m) 55 dB(A)